Sevikabel

    Italian - ItalyEnglish (United Kingdom)
  • Mappa del sito

  • *
    *
    *
    *
    *
    Fields marked with an asterisk (*) are required.

StampaE-mail

SILICOUL 3.7KV (+180°C)

Chiedi un'informazione riguardo questo prodotto

 

alt

alt
alt

SILICOUL® 3.7KV
alt
(-60°C + 180°C)
CLASSE H - Treccia speciale in fibra sintetica
1) COND.: RAME STAGNATO CLASSE 5 IEC 228
2) NASTRO SEPARATORE
3) ISOLAMENTO: GOMMA SILICONE
4) TRECCIA SPECIALE IN FIBRA SINTETICA COL. MARRONE
1) TINNED COPPER CORE - CLASS 5 - IEC 228
2) SEPARATING TAPE
3) SILICONE RUBBER
4) COATED SYNTHETIC REINFORCING BRAID BROWN

• CARATTERISTICHE
• Generali
• Temperatura ammissibile : -60 +180°C.
• Temperatura di punta : +230°C.
- Buona resistenza agli shock termici e UV
- Buona resistenza all'Ozono e all'effetto corona
- Eccellente resistenza meccanica
- Eccellente resistenza in atmosfera chimica abituale
- Compatibile con la maggior parte delle vernici di impregnazione
- Raggio di curvatura = 5 x d.

• ELETTRICHE

- Tensione nominale: 4.2 KV - Tens. di prova: 10 KV

• PRODUZIONE STANDARD
• Tutte le sezioni : colore esterno marrone

• OPZIONI
• Altre tensioni nominali: 1,1 KV - 6.6 KV, 13.8 KV

• CONFEZIONAMENTO
• Bobine, Matasse

• NORME ed OMOLOGAZIONI

- Emissione fumi classe F1 secondo NF F 16-101
- Certificato di approvazione per l'applicazione marina norma
- n° IEC 60092-350 Lloyd's Registro of Shipping
- Comportamento al Fuoco2
- conforme ai test IEC 60331, IEC 60332-1 e IEC 60332-3

• APPLICAZIONE
• Cablaggi interni di motori elettrici trasformatori, macchine
Eelettriche in classe H.
- Costruzioni Navali e Ferroviarie
- Armonizzatori di energia

• CHARACTERISTICS
• General
• Working temperature: - 60°C to +180°C
- Peaks at + 230°C.
- Good resistance to thermal shock and UV.
- Good resistance to ozone and the corona effect.
- Excellent mechanical strength.
- Bending radius 5 x d.
- Compatible with most impregnation varnishes.nation varnishes.

• ELECTRICAL

- Working voltage: 4.2 KV - Test voltage: 10 KV

• STANDARD PRODUCTS
• All cross sections : Colours Brown


• OPTIONS
• Other working voltages: 1.1 KV - 6.6 KV, 13.8 KV

• PACKAGING

• Spools, drums

• STANDARDS and APPROVALS

- F1 rated as per NF F 16-101.
- Type approval certificates for use in shipbuilding
- industry, IEC 60092-350 standards.
- Lloyd’s Register of Shipping.
- Fire behaviour : Meets requirements of IEC 60331,
- IEC 60332-1 et IEC 60332-3 tests.

• USE
- Applications: Wiring of rotating machines: motors, alternators,
- generators. - Wiring of static machines: transformers, inductors,
- inverters, choppers.
- Shipbuilding and railway construction. Power supply.


SU RICHIESTA DEL CLIENTE: OMOLOGAZIONE UL 4.2 KV STYLE 3662
alt alt
OPTIONS: HOMOLOGATION UL 4.2 KV STYLE 3662

Codice
Code
Sezione
Cross-section
mm2
Composizione
Stranding
Resistenza
Core Resistance
(20°C)
Diametro Esterno
Outer Diameter
Massa
Weight
kg/km
-
*2.5
50 x 0.25
8.21
6.2
57.0
-
*4
56 x 0.30
5.09
6.8
75.0
-
6
84 x 0.30
3.39
7.8
102
-
10
80 x 0.40
1.95
9.0
150
-
16
126 x 0.40
1.24
10.2
212
-
25
196 x 0.40
0.795
11.8
305
-
35
276 x 0.40
0.565
13.2
413
-
50
396 x 0.40
0.393
15.4
575
-
70
360 x 0.50
0.277
17.0
782
-
95
485 x 0.50
0.210
19.8
1030
-
120
608 x 0.50
0.164
21.8
1290
-
150
756 x 0.50
0.132
24.0
1580
-
185
944 x 0.50
0.108
25.4
1890
-
240
1221 x 0.50
0.0817
29.2
2451
-
300
1525 x 0.50
0.0654
31.8
3120
-
400
2037 x 0.50
0.0495
35.8
4160

*Senza nastro separatore / No separating tape - *Valore nominale / Valeurs nominales / Nominal values / Nominalwerte

alt