Construction features

PVC Insulated Electrical Conductors

- NATURE OF CONDUCTOR: CLASS 5 RED COPPER

- PRIMARY INSULATION: PVC ACCORDING TO VDE 0207 § 4

- IDENTIFICATION OF CONDUCTORS:
BLACK NUMBERED + G/GREEN

- OUTER SHEATH: GREY PVC RAL 7001 SELF-EXTINGUISHING, FLAME RETARDANT ACCORDING TO IEC 332.1 VDE 0472
§ 804, VW1, CSA FT1, HD405.1

- OIL RESISTANT: HD 505.2.1 § 10
UL 1581 § 50.182, VDE 0472 § 803

Respected standards

Standards and approvals

VDE0281 PARAG. 13 HD 21.13 S1.
UL - STYLE 2517/2587 and CSA C22.2 NO 210-M2-M90

Use

ALL MACHINE BUILDERS AND INSTALLERS WHO EXPORT WORLDWIDE USING THIS CABLE BENEFIT FROM TRIPLE SAFETY, WITH UL - CSA - HAR APPROVALS

Technical specifications

Service temperature
HAR -5°C + 70°C UL + CSA -5°C + 90°C
Nominal tension
HAR 300 / 500 V UL + CSA 0.5 1.5 : 300 V UL + CSA 2.5 : 600 V
Test voltage
2000 V at 60 Hz
Bend Radius Dynamic
10 X D. EXTERNAL CABLE