Construction features

General characteristics: 

The cable has good resistance to acids and bases and excellent resistance to hydrocarbons

  • Water resistance: type AD7 according to IEC 60529 without immersion of the ends
  • UV resistance ≥ 2 000 h according to EN 16472.

Thermal characteristics: 

  • Continuous service temperature: -30°C to +80°C.
  • Maximum conductor temperature: +90°C

Electrical characteristics: 

  • Rated voltage:600/1000 V.
  • Test voltage: 3500 V.

Standard production: 

  • Sheath: orange
  • Finding conductors:
    o Up to 5 conductors: according to HD 308 S2
    o More than 5 conductors: white numbered

Standards and approvals

  • IEC 60228 / NF C 32-090
  • IEC 60332-1 / IEC 60332-3 / NF C 32-070 test C1
  • IEC 60331-21 / NF EN 50200
  • IEC 61034-2 / IEC 60754-1 / IEC 60754-2.

Fire and smoke behaviour

  • Non-flame propagating - on single cable: IEC 60332-1-2/ NF EN 60332-1-2 / NF C 32-70 test C2.
  • Flame-retardant - on cable bundle: IEC 60332-3-22 cat. A / NF EN 60332-3-22 cat. A
  • Non-combustible: NF C 32-070 test C1
  • Fire resistance: IEC 60331-21 / NF EN 50200
  • Low smoke density: IEC 61034-2 / NF EN 61034-2
  • Halogen-free: IEC 60754-1 / NF EN 60754-1
  • Low corrosivity of emitted gases: IEC 60754-2 / NF EN 60754-2

Options

  • FLEX: flexible tinned copper conductor, class 5 according to IEC 60228
  • Other colours: consult us
  • Cable at 105°C: consult us
  • ATEX according to NF C 15-100 Part 4-42/ EN 60079-14- Particularly suitable for fixed installations in explosion hazardous areas, without intrinsic protection mode “i”.”
  • ENERSYL® FR BG EX POWER : with HFFR sheathing under the reinforcement and without hygroscopic separator tape

Technical specifications

Service temperature
-30 °C to +80 °C.
Peak temperature
+90°C
Nominal tension
600/1000V
Test voltage
3500V