Multi-core shielded fire retardant cable CR1-C1 IEC 60331-21
Max. conductor temperature: +90°C
- Conductor: Class 1 rigid red copper - Ø 0.9 mm
- Insulation: EI2 fire resistant elastomer
- Electrical screen: metal tape + continuity wire
- Outer sheath: LSZH halogen-free flame-retardant polyolefin rubber (T) or EI2 fire-resistant elastomer (E)
Minimum bending radius: 10 x D
Electrical characteristics:
- Rated voltage: 100/170 V
Standard production:
- Outer sheath: orange
- Fire resistant according to NF C 32-070 test CR1
- Fire resistant according to IEC 60331-21, 90 minutes.
- Not fire propagating according to NF C 32-070 test C1, IEC 60332-3-22 and IEC 60332-3-24.
- Flame-retardant according to NF C 32-070 test C2 and IEC 60332-1-2.
- Halogen-free according to IEC 60754-1
- Non-corrosiveness of fumes according to IEC 60754-2.
- Low smoke opacity according to IEC 61034.
- Allowed for use of the NF-USE mark according to NF C 32-070 and NF C 32-310.
- Individual + general screen: ref. SILIFLAM 500 TEL EI/EG
- Fire safety wiring.
- Telephone transmissions.
- Telemetering and control systems.
- PYRITEL® 100 EN cables are not designed for underground laying.
coils
Service temperature+90°C
Nominal tension100/170V
Bending Radius Static≥ 10 x cable outer Ø