Reinforced cable with special RH + UV PVC insulation - Recommended for ATEX zones.
Continuous service temperature: -25°C to +60°C
Cable composition:
- Red copper conductor - class 1 or 2 according to IEC 60228 and according to sections
- Insulation: Cross-linked polyethylene (XLPE)
- Inner sheath: thermoplastic
- Reinforcement: two helical steel sheets (0.2 mm thick) overlapping
- Outer sheath: special black PVC in RH + UV quality
Electrical characteristics:
- Rated voltage:
- 600/1000V AC
- 900/1500V DC
- Test voltage:
- 3500 AC for 5 minutes
- 8400 DC for 5 minutes
General characteristics:
- Bending radius: 10 x D (fixed)
Standard production:
- Outer mark: NF USE U -1000 RVFV - n G s - lot
- Identification of conductors: colours according to HD 308 S2
Installation
- Without additional mechanical protection, in free air, these cables can be installed in a fixed position on walls or cable trays or other supports.
- For direct laying underground without protection.
- In hazardous areas BE3 must be installed with appropriate electrical protection. In this case, the permissible intensities of 15% must be reduced (see recommendations according to installation standard NF C 15-100 art. 424-8-BE3).
- NF C 32-322 / XP C 32-322 (sheathing resistant to extreme climatic conditions and UV radiation): rigid cables insulated with cross-linked polyethylene with PVC sheathing, armoured - series U-1000 RVFV.
- Not flame propagating: IEC 60332-1 / NF C 32-070 2.1 category C2.
- Climate resistance testing, including UV.
- RoHS: European Directive 2011/65/EU.
- Construction Products Regulation 305/2011.
- Euroclass according to RPC: Eca.
- Conductor according to IEC 60228:
- cross-section 1.5mm² to 4mm²: class 1
- 6mm² to 185mm²: class 2
- For industrial installations requiring reinforced protection.
- Recommended in ATEX zones.
- Outer sheath made of special RH-quality PVC, suitable for aliphatic hydrocarbons. If aromatic hydrocarbons are present, special sheathing type PF or TF (ETFE) must be used.
- Electrically powered property portals.
- Anti-rodent protection.
Service temperature-25°C + 60°C
Nominal tension600/1000V AC - 900/1500V DC
Test voltage3500V AC 5 min - 8400V DC 5 min
Bending Radius Static10x cable outer Ø