Construction features

General characteristics: 

  • Good resistance to acids.
  • Fairly good resistance to bases.
  • Good resistance to aliphatic hydrocarbons.
  • Water resistance: type AD7 according to IEC 60529 without immersion of the ends
  • UV resistance ≥ 2 000 hours according to IEC 16472

Thermal characteristics: 

  • Continuous service temperature: -30 °C to +80 °C.
  • Maximum conductor temperature: +90°C

Electrical characteristics: 

  • Rated voltage:300/500 V.
  • Test voltage: 2000 V.

Standards and approvals

  • IEC 60228
  • IEC 60332-1 / IEC 60332-3
  • IEC 61034-2 / IEC 60754-1 / IEC 60754-2

Fire and smoke behaviour: 

  • Flame-retardant - single cable : IEC 60332-1-2/ NF EN 60332-1-2/ NF C 32-070 test C2
  • Flame-retardant - cable harness: IEC 60332-3-24 cat. C / NF EN 60332-3-24 cat. C
  • Low smoke density: IEC 61034-2 / NF EN 61034-2
  • Halogen-free: IEC 60754-1 / NF EN 60754-1
  • Low corrosivity of emitted gases: IEC 60754-2 / NF EN 60754-2

Options

  •  FLEX: flexible tinned copper conductor - class 5 according to IEC 60228 (cross-section 0.9mm² replaced by 1mm²)
  • C1fire retardant cable according to NF C 070 test C1: consult us
  • Other colours: consult us
  • Other colours: consult us
  • ATEX according to EN 60079-14
    Particularly suitable for fixed installations in explosion-hazardous environments, with an intrinsically safe protection mode “i” requiring special cable marking.
  • Sheath colourblue according to EN 60079-14 part 12.2.2.6
    o ENERSYL® ZH EI BE EX INSTRUM: with individual (aluminium/PET tape) and general (tinned copper braid) electrical shielding
    o ENERSYL® ZH EI EX INSTRUM: with individual and general electric screen (aluminium/PET tape)
    o ENERSYL® ZH BE EX INSTRUM: with general electric screen (tinned copper braid)
    o ENERSYL® ZH EG EX INSTRUM : with general electric screen (aluminium/PET tape)

Use

Particularly suitable for fixed installations in explosion-hazardous environments, with intrinsic safety protection mode “i”

Technical specifications

Service temperature
-30 °C to +80 °C.
Peak temperature
+90°C
Nominal tension
300/500 V
Test voltage
2000V