General characteristics:
- Good resistance to acids.
- Fairly good resistance to bases.
- Good resistance to aliphatic hydrocarbons.
- Water resistance: type AD7 according to IEC 60529 without immersion of the ends
- UV resistance ≥ 2 000 hours according to IEC 16472
Thermal characteristics:
- Continuous service temperature: -30 °C to +80 °C.
- Maximum conductor temperature: +90°C
Electrical characteristics:
- Rated voltage:300/500 V.
- Test voltage: 2000 V.
- IEC 60228
- IEC 60332-1 / IEC 60332-3
- IEC 61034-2 / IEC 60754-1 / IEC 60754-2
Fire and smoke behaviour:
- Flame-retardant - single cable : IEC 60332-1-2/ NF EN 60332-1-2/ NF C 32-070 test C2
- Flame-retardant - cable harness: IEC 60332-3-24 cat. C / NF EN 60332-3-24 cat. C
- Low smoke density: IEC 61034-2 / NF EN 61034-2
- Halogen-free: IEC 60754-1 / NF EN 60754-1
- Low corrosivity of emitted gases: IEC 60754-2 / NF EN 60754-2
- FLEX: flexible tinned copper conductor - class 5 according to IEC 60228 (cross-section 0.9mm² replaced by 1mm²)
- C1fire retardant cable according to NF C 070 test C1: consult us
- Other colours: consult us
- Other colours: consult us
- ATEX according to EN 60079-14
Particularly suitable for fixed installations in explosion-hazardous environments, with an intrinsically safe protection mode “i” requiring special cable marking. - Sheath colourblue according to EN 60079-14 part 12.2.2.6
o ENERSYL® ZH EI BE EX INSTRUM: with individual (aluminium/PET tape) and general (tinned copper braid) electrical shielding
o ENERSYL® ZH EI EX INSTRUM: with individual and general electric screen (aluminium/PET tape)
o ENERSYL® ZH BE EX INSTRUM: with general electric screen (tinned copper braid)
o ENERSYL® ZH EG EX INSTRUM : with general electric screen (aluminium/PET tape)
Particularly suitable for fixed installations in explosion-hazardous environments, with intrinsic safety protection mode “i”
Service temperature-30 °C to +80 °C.
Peak temperature+90°C
Nominal tension300/500 V
Test voltage2000V